Basic Information
Place of Origin: Sichuan, CHINA
Brand Name: IOTROUTER
Certification: CE FCC RoHs
Model Number: ZHC1921
Minimum Order Quantity: 1PCS
Price: USD45~48/PCS
Packaging Details: 270*180*55mm CARTON PACKAGE
Delivery Time: 1 WEEK
Payment Terms: L/C, T/T, Western Union
Supply Ability: 50000PCS/MONTH
Material: Galvanized Steel Sheet Interface: RS485/6DI/4DO/4AI
Protocol: MODBUS TCP/RTU MQTT Product Name: 16 Channel Rj45 Ethernet IO Controller
Function: Pulse Counting System Application: Data Acquisition Solutions
Working Voltage: 12V Module Type: Ethernet
Customized: Support
High Light:

Rj45 Ethernet IO Controller

,

16 Channel Ethernet IO Controller

,

Data Acquisition Modbus Rtu Controller

16 Channel Rj45 Ethernet IO Controller Modbus RTU For Data Acquisition Solutions

 

 

Parameters of ZHC1921

 

POWER
NETWORK
POWER SUPPLY
9~36V
NETWORK TYPE
ETHERNET
 
Working Current
200mA(aver)/340mA(max)@9V
NUMBER
LAN*1
50mA(aver)/850mA(max)@36V
PORT TYPE
Ethernet signal, RJ45
SERIAL PORT
DO
Serial Port
RS485*1
Standard
(NO,COM)*4
Standard
RS485: 2 Two terminals(A,B)
AC
250V 10A
Baud rate
600~921600bps
DC
30V 10A
Data bits
8, 9
DI
Stop bits
0.5, 1, 1.5, 2
Standard
DI*6 COM*1
Parity bits
NONE,EVEN,ODD
Detect Range
5~50v High 0~2v Low
PI
AI
Number
1
Number
4
Standard
PI*2 COM*1
Standard
AI*4 COM*2
Detect Range
10000Hz
Detect Range
4~20mA


Introduction​ of ZHC1921

 

ZHC1921 is a network IO product that supports 6-way dry (wet) node detection, 4-way relay (COM, NO) output, 4-way analog (current 4~20mA) detection, and 1-way serial port transparent transmission, compatible with Modbus RTU/TCP protocol. With "remote control" as the core of the function, it is highly easy to use, and users can easily and quickly integrate into their own systems to achieve remote based on Ethernet and RS485 with Local control.

 

 

Reset Method


The device can be restored to the field settings by operating the RESET button.
Steps:
Step 1: Power on the device.
Step 2: Press and hold the RESET button until the indicator lights of the device are all off, and immediately release the reset button, the device is restored to factory settings successfully.
If the serial port of the device is found to actively send JSON packets after reset, it indicates that the reset button has been pressed for too long and the device enters the local firmware upgrade mode. At this time, power off the device and perform the reset operation again.

 

 

The default IP address of ZHC1921 is 192.168.0.65. The configuration requires that the computer and ZHC1921 IP be set to the same IP address segment, otherwise the device and the computer cannot communicate.
ZHC1921 has built-in parameter configuration webpage. Users who use this device do not need to pay attention to the relevant holding registers of the device. They only need to understand the reported data of the device.

 

 

Set up ZHC1921 then use the Ethernet cable to connect the network port of the network device (router/switch/other) with ZHC1921. After the device is powered on, observe that the WORK indicator should flash for 3s, indicating that the network hardware environment where the device is located is normal and Ethernet data can be exchanged.

 

 

16 Channel Rj45 Ethernet IO Controller Data Acquisition Modbus Rtu Controller 0

16 Channel Rj45 Ethernet IO Controller Data Acquisition Modbus Rtu Controller 1

16 Channel Rj45 Ethernet IO Controller Data Acquisition Modbus Rtu Controller 2

16 Channel Rj45 Ethernet IO Controller Data Acquisition Modbus Rtu Controller 3

16 Channel Rj45 Ethernet IO Controller Data Acquisition Modbus Rtu Controller 4

16 Channel Rj45 Ethernet IO Controller Data Acquisition Modbus Rtu Controller 5

16 Channel Rj45 Ethernet IO Controller Data Acquisition Modbus Rtu Controller 6

16 Channel Rj45 Ethernet IO Controller Data Acquisition Modbus Rtu Controller 7

 

 

ZHC1921

RS485 Modbus

RS485 Automatic Acquisition

Virtual Serial Port

Connfiguration Software

Threshold Report

4 Channel Socket

Customize the Follow Logic of Ports

MQTT/Modbus RTU/TCP